I opened my pool two weeks ago. At the time, I was able to fire up the heater and it ran for about 20 minutes before mysteriously shutting down. I decided to troubleshoot this on my own which may have been my first mistake
I used the troubleshooting guide in the "Workbook JXi Pool & Spa Heater" provided by Zodiac.
Background:
Saltwater Pool & Spa
Built in 2015
All Jandy equipment
When I use the Aqualink remote to turn on the heater, I choose a temperature well above the current water temp.
Behavior
According to the troubleshooting manual, I was supposed to skip to step 13 if the blower was on and working. Everything else seemed to checkout. I have now replaced:
Any help or suggestions about what might be the cause of this? I am at a loss and don't want to waste any more money on parts until I am sure of what it might be. Any and all advice is welcome.
Thanks,
Mike
Background:
Saltwater Pool & Spa
Built in 2015
All Jandy equipment
When I use the Aqualink remote to turn on the heater, I choose a temperature well above the current water temp.
Behavior
- Heater Blower turns on and remains on
- Igniter glows
- Hear a clicking sound, ignitor stops glowing
- Approx 30 seconds later Ignitor begins glowing again, same as above
- Tries 3rd time, then shuts down
According to the troubleshooting manual, I was supposed to skip to step 13 if the blower was on and working. Everything else seemed to checkout. I have now replaced:
- The Gas Valve
- Water Pressure Switch - Brass nuts were cracked anyway
- Ignition Control
- I noted that the two wires connected to the Exhaust Temp Fusible Link, were blackened and charred. I cut those ends off and re-crimped new ends, but did not attempt to replace the Exhaust Temp switch. According to the troubleshooting steps in the manual, the fusible link was fine. Could that possibly be the issue? (See Photo)
- It does not seem like the gas valve is opening and releasing gas
- The main gas Valve is on
- Gas pressure incoming is measured at 7.6 in WC
Thanks,
Mike