Hi folks,
First time poster
I have a real mystery that I am hoping I can find a solution to. I have a Jandy JXi series heater connected to a Hayward Omnihub through the 2 wire (fireman's switch) for remote control. AFAIK, Everything is set according to the manufacturer's instructions:
- On Jandy, 2 wire connected to POOL + COM contacts
- On Jandy, RTSTAT is set and thermostat set to 104 degrees
- On Hayward 2 wire connected to LVR1 (low voltage relay)
- On Hayward, heater is programmed to the LVR1
The problem I am having is that regardless of the setting of the Omnihub, the heater is always on and heating. Here are some of my diagnostic efforts:
- Tested remote wire for shorts with a multi-meter
- Connected multi-meter (in continuity mode) to Omnihub to verify contact closing/opening properly (set point below water temp == contact open; set point above water temp == contact closed) PASSED.
- Manually opened and closed the circuit on the Jandy (in RTSTAT mode, connected COM to POOL contacts and heater came on; disconnected COM from POOL contacts and heater turned off) PASSED.
If I had any hair left I would be pulling it out

If anyone knows why the pieces seem to be working as expected separately but not together PLEASE HELP!
Thank you in advance for any assistance.
Best regards,
Ken