I did this without the regulator for a couple of minutes. It got to 230 I think, although it was dark out. I don't have any error lights or anything on. Maybe it was 290? How long should I wait to let it get up to temp (I had just started it up so this was in the first few minutes). I can try again in the morning but what would this mean if it was low (and wouldn't I have the service heater light on?)You should also check the exhaust gas temperature during operation.
Excessive temperatures indicate low water flow.
Exhaust Gas Temperature.
While running, press and hold the On button to display the exhaust temperature (Older Models).
The new models use the Menu to get the SFS.
Here is what the normal exhaust temperature should be:
Note: HD models can be up to 75 degrees higher. HD models use a cupro nickel exchanger and the efficiency is slightly lower resulting in less heat transfer and more waste heat.
- Below 250 degrees...very low
- 250 to 290 ..................low
- 290 to 350.................acceptable
- 350 to 480 ..................high
- Above 480...................error/shutdown.
Pentair MasterTemp Heaters - Further Reading
www.troublefreepool.com
The only lights on it right now are heating and spa on. Held the spa button down for a few and got 267.If the temperature is too low, it won't give an error.
However, it would probably error out due to flame sensing because a low temperature is probably due to a weak flame.
Didn't do any of that or look at the flame. Currently, with the regulator out, there is no whistling/whining. I would assume if it was a gas problem, it would persist with or without the regulator in?Whistling can also be a gas problem. Was a manometer used to check the gas valve at static and while running to verify the psi. The heater label should state the specifications for it. What color is the flame.
What color is the flame.
Forgot which heaterThe MasterTemp heater has a sealed burner can and you cannot see the flame.
15,400 gallons is 128,436 lbs.brought the temp up from 68 to 71 in less than 2 hours this morning...
That's about what I get actually. I've always got around 1.5 degrees per hour. Looking at the history from screen logic, getting one degree every 40 minutes.15,400 gallons is 128,436 lbs.
A 250,000 btu/hr heater at 84% efficiency provides 210,000 btu/hr to the water.
So, you should get 1.6 degrees per hour.
Watch the gas meter.
You should use about 250 cubic feet per hour for the heater.
Don't really have any way to calculate flow rate I know of. At 120 degrees it won't open - not until it gets to 130. Same as the other one. I'm at my inlaws doing water glass tests because the store is a 45 minute drive from me, but right by my inlawsDoes it open 100% at 120 degrees?
What is the flow rate?
What is the stack flue temperature with the regulator in?
The book says that if it is not open at 120 degrees to replace it.At 120 degrees it won't open
You can put the system in Service Mode to use the control panel on the pump to calibrate the flow at different speeds.Don't really have any way to calculate flow rate I know of.
I'm with you on the stamp!The book says that if it is not open at 120 degrees to replace it.
The part says 120 F stamped right on the part, so that is when it needs to open.
It does not say 121 degrees or 122 degrees or 130 degrees.
Maybe contact Pentair to see what they say.
![]()
![]()
You can put the system in Service Mode to use the control panel on the pump to calibrate the flow at different speeds.
View attachment 494412
Press the "On" button for the mode that is on.my panel is extremely finicky and I'll be darned if I can get the flue temp to come up again.