Since you have open breaker slots I would add a 120V 20A GFCI CB and move the lights to that breaker. Move the green dot hot wire on my pic above that powers the controller to go directly into the existing 120V CB.
That keeps your controller on a separate CB from your lights. Should your lights trip the GFCI your controller will not go down. Otherwise having a GFCI problem with your lights can shutdown the controller and your entire pool.
Your actual loads is around 18 amps between your pump, blower, lights and controller. Adding another breaker and separating the lights and controller to separate breakers adds no additional loads to the panel.
Leave the controller on the existing 120V breaker and add a 120V GFCI CB for the lights.
Changing the pump CB to a GFCI is easy. I don't understand your reluctance to increase the safety. I don't understand what neutrals you are musing about. A 240V pump does not have any neutrals. Your pump is on and electrified much more then your lights are.
Having a GFCI breaker won't protect your controller from electrical surges.I put in the breaker this way, but wondering now if it would be better to keep the controller protected on the GFCI. If you look at the picture of the entire unit, you can see the LCD took a beating from the lightning.
The neutral out goes to the neutral bar.Mostly concerned about neutrals because the 2-pole QP GFCI has a neutral out and nothing will be going in.
Thanks for all this. I put in the breaker this way, but wondering now if it would be better to keep the controller protected on the GFCI. If you look at the picture of the entire unit, you can see the LCD took a beating from the lightning.
Does it really matter if the controller goes down with the lights? I guess only if it's down for an extended period? If there is an issue, either I can reset the GFCI or I'm replacing breakers and maybe equipment.
Could always put the controller back on the regular breaker if there is an extended problem. Am I missing something?
Mostly concerned about neutrals because the 2-pole QP GFCI has a neutral out and nothing will be going in. Looking at the Siemens QF220 as an example. What do I do with the neutral from the GFCI CB?
Is that the wrong CB for 240v with no neutrals?
On a 2-pole 240v GFCB, the neutral wire from the breaker is hooked to the neutral bus. If you don't do that it won't "test." No neutral to the motor. A 2-pole GFCB measures the current on each leg and if they get out of balance by 5mA it will trip to protect you, not the equipment.Thanks for all this. I put in the breaker this way, but wondering now if it would be better to keep the controller protected on the GFCI. If you look at the picture of the entire unit, you can see the LCD took a beating from the lightning. Does it really matter if the controller goes down with the lights? I guess only if it's down for an extended period? If there is an issue, either I can reset the GFCI or I'm replacing breakers and maybe equipment. Could always put the controller back on the regular breaker if there is an extended problem. Am I missing something?
Here's the installed GFCI:
View attachment 460850
I see the lights as more of a concern because there are wires in the water with my kids. The pump is 30' away, and wasn't considered an issue until relatively recently as far as code.
Mostly concerned about neutrals because the 2-pole QP GFCI has a neutral out and nothing will be going in. Looking at the Siemens QF220 as an example. What do I do with the neutral from the GFCI CB? Is that the wrong CB for 240v with no neutrals?
I'm pretty skeptical of surge protectors these days. I have some good ones, and they made no difference as to what got fried. All my GFIs were tripped in the house, and anything that was attached to them was fine.Having a GFCI breaker won't protect your controller from electrical surges.
Electrical Surge Protection - Further Reading
www.troublefreepool.com
GFCI CB may not reset with a light ground fault problem. And fixing a light ground fault may take a while to diagnose and fix.
You will not have a regular breaker to put the controller onto unless you leave your old one in. In which case just connect the controller power to it now which looks like you did..
Neutral from the 240V GFCI CB connects to the neutral bus. There is no neutral wires connected in a 240V circuit. It is the correct CB.
You only have a neutral connected to the CB if you use one side of the 240V CB to power a 120V load.
They are 120v with 12AWG wiring I believe. Both are currently Hayward, but I have to change the pool light because ColorLogic isn't serviceable. I've heard there's a way to change the light engine with a Pentair part, but I'm not looking to mess with that. So, I'll probably replace it with a Hayward Astrolite, if that's the best option, and add an LED bulb. In that case, I expect the wiring will be the same size but I won't know until I get it.If your lights are sharing a neutral and ground, you need to make sure that they are sized correctly.
What is the power rating for your lights?
What is the wire size for the neutral and ground?
On a 2-pole 240v GFCB, the neutral wire from the breaker is hooked to the neutral bus. If you don't do that it won't "test." No neutral to the motor. A 2-pole GFCB measures the current on each leg and if they get out of balance by 5mA it will trip to protect you, not the equipment.
A GFCI device protects people, not equipment. Having one, or not having one, on the pool control is up to you.
Very low watt LED bulbs. I think the Spa bulb is 35 watts. Not sure exactly what bulb I will get for the pool, but I expect it will be 35-50watts in a fixture made for a 400w - 500w bulb.Do you know the watts or amps for the lights?
Based on the 2 lights not drawing much power?I would have used a 15 amp breaker.
In my opinion, a 20 amp breaker is oversized for the application.
Assuming the light wires are #14 AWG copper, the maximum allowable breaker is 15 amps.
There's a remanent of something on top of the jacket, the wire is fine. Can't tell exactly what it was, probably labeling the wire. I'll cut it off or cut the wire back behind that so an inspector doesn't draw the same conclusion in the future.This wire is damaged and it should be replaced (Red Arrow).
I would replace both single pole breakers with 15 amp GFCI breakers and the double pole breaker with a 20 amp GFCI breaker (assuming the pump wires are #12 AWG copper).