Can you show the main ground rod for the property?So the only way to test is to have the power company do it?
Can you show the main ground rod for the property?So the only way to test is to have the power company do it?
I attempted an NEV test I noted in post 67Was the neutral current measured? That wasn't clear to me from that statement. If NEV is 2 v and a typical grounding rod as an equivalent resistance of 25 ohms to real ground (NEC max), then the current would be only 80 ma. What was the range setting of the amp meter? Was it an analog or digital meter? Maybe he just didn't have the correct settings to see it.
Anyway a separate voltage test is very easy to do and would confirm if there is or is not NEV. You only have to be about 3 ground rod lengths away from the grounding rod to get 95% of the voltage. It drops off pretty fast with distance. Put a screw driver in the ground and measure the voltage difference between the screw driver shaft and the house neutral/ground.
I think the inspector was competent. He also called 4 colleagues to explain the situation to see if they had other ideas.If the inspector said that it was safe, I don't know that I would be too worried about it.
You have probably done about as much as you can do.
Unless you can find a good electrician who knows what to check, you have probably done what can be done.
If people report any problems, then check it out farther.
In general, do you feel comfortable that the inspector was competent in their assessment?
NEVsetup2 - NEV setup (screwdriver in ground 6-8' from meter connected to wire)
NEVMeterRead - reading on the meter
NEV-HeatPumpBond - reading on bond nut of heat pump
NEV-PoolWater - reading in water
Not shown, the handrail and ladder read the same as the pool/bond wire points - right around 1v.
Also not pictured, the point where I keep getting the higher voltage 1.2v and the .59 mA in Pic 1, is a bolt on the slide... the NEV read was in line or a little less than the meter read.
Although it looks close, The screw driver is 6-10’ from the meter. I did touch the metal paint on the meter (.29). I also touched the ground wire where the cable attached to the meter (1v). If I use the 1v reference instead the other readings are much more in line.Sorry I missed this
The screw driver is a little close to the meter so the voltage will be less than it would further away but given you did measure a voltage, that indicates a voltage on the neutral relative to earth ground (NEV).
Were all of these tests performed relative to the same screw driver location?
What did you touch for the meter reading? The painted case is not a very good contact. The ground terminal of an outlet would be a better choice.
Ok, that makes more sense. It looks like there is some NEV and most likely the voltage varies over the course of the day depending on the network load. So it may or may not be a long term issue.Although it looks close, The screw driver is 6-10’ from the meter. I did touch the metal paint on the meter (.29). I also touched the ground wire where the cable attached to the meter (1v). If I use the 1v reference instead the other readings are much more in line.
What would be a normal and acceptable level and what would constitute a level that would be cause for concern?It looks like there is some NEV and most likely the voltage varies over the course of the day depending on the network load.
That stuff will wear off quite quickly.From what I have read, most power companies do not get too concerned until it gets above 4v. This is from my PC:
Given you need more than 10x that amount to have even the smallest risk of death, that is not unreasonable. However, that doesn't mean it isn't uncomfortable and a nuisance.
Just thinking out loud and maybe a crackpot idea but what about conductive paint on the deck surface with a bonding plate(s) close to the hot spots. It might help and a lot cheaper than a new deck.
![]()
Conductive transparent paint.
Aerosol permanently conductive graphene hybrid transparent acrylic paint. Applications in lighting, windows, clear covers and lids, displays etc.hollandshielding.com
How deep should you place the rods? How do you know if this will work or make it worse? Did you do some kind of ground study?Note: Only consider doing something like this if you have approval of a qualified professional like an engineer or other such qualified professional.
What if you put copper ground rods around the pool at maybe 2 to 4 foot apart and run a copper bond wire so that it connects to each ground rod?
This should essentially form a Faraday cage around the entire area and any stray current would (theoretically) be intercepted and routed around the protected area.
You could tie it into the existing bonding grid.
This would be a lot of work and a lot of money, but it might help.
There’s always a risk that you would hit something underground like a utility line, power, water, gas, sewer etc. and cause damage.
There’s also a risk that it might make things worse depending on what is causing the stray current/voltage.
ERICO. 5/8 in. x 8 ft. Copper Ground Rod.
Internet #202195738
Model #615880UPC
Store SKU #687693
$20.94
ERICO copper-bonded ground rods are the highest quality ground rods available today.
We use a unique manufacturing process, which includes drawing the steel rod to size before the copper bonding process begins.
This results in a straighter, harder steel core, making installation easier.
ERICO uses a continuous electro-plating process over the steel core that results in a permanent molecular bond that provides decades of reliable performance.
Our state-of-the-art ISO registered manufacturing facility provides a consistent, high-quality finished product that is used in millions of installations around the world.
99.9% pure electrolytic copper coating
Molecular bond to nickel-sealed high strength steel core
Rods have a high carbon steel core and tip that provide superior strength when driving
Copper coating will not crack when bent or tear when driven
Minimum copper coating of 10 mils on rods listed to UL- 467
ERICO name, length, diameter and part number is roll-stamped within 12" (304,8 mm) of chamfered end
UL logo and control number where applicable stamped on each rod for easy inspection after installation
![]()
ERICO 5/8 in. x 8 ft. Copper Grounding Bar Rod 615880UPC - The Home Depot
Protect your home and family from electrical shock with this ERITECH Copper Ground Rod. UL certified product for added protection.www.homedepot.com