Sorry guys… another IntelliCenter question. How to I adjust the VS pump speeds for programming? I don’t see an option to do that in the panel. I can set start and end times but not speed. Thanks!!
I have a weird feeling that they didn’t run cables from the pumps to the IntelliCenter. I’ll check tomorrow…Are the pumps connected via the RS485 network? There is a small plug on the side of the control head. That should have a quick connector in it and be ran back to the panel.
You will need to make sure those are added and addressed properly before you can associate any pump speeds to them.
--Jeff
They are Pentair VS+SVRS pumps.Joel.
What kind of pumps are they???
Jim R.
I’m sure this is what’s going on. It’s basically just turning the pump on and off. Like a fancy light switch.Could the pump relay in the Intellicenter be controlling power to the pump and not actual speed ?
So it’s acting like a one speed pump and either on or off depending on scheduling?
Just a thought.
I had to order the communications cable for my pump separate.