It's time to replace the deteriorating and getting louder by the day single speed pump. It is currently plumbed with the return line tucked nearly against the pump housing. The Superflow VS that is replacing it is too wide for that arrangement by about 4 inches or so.



Two options I'm looking at are:
1. Shorten the long horizontal run that contains the chlorine generator. This would add a couple of 45s to the vertical.
2. 45 out from the skimmer & main drain valve. Doing this, I could simplify the series of 3 90s in the vertical run coming down into the pump, I could reduce it to 1 90.
Is there any advantage to either approach? Is there something else I should be considering?
Also, we have at least a week ahead with temps dropping into the teens at night. I hope the current pump lasts until the weather warms up, but if it goes out completely, what happens if I replace the pump and don't wait 24 hours before starting up the system? My concern is that the PVC glue won't have adequate time to set.



Two options I'm looking at are:
1. Shorten the long horizontal run that contains the chlorine generator. This would add a couple of 45s to the vertical.
2. 45 out from the skimmer & main drain valve. Doing this, I could simplify the series of 3 90s in the vertical run coming down into the pump, I could reduce it to 1 90.
Is there any advantage to either approach? Is there something else I should be considering?
Also, we have at least a week ahead with temps dropping into the teens at night. I hope the current pump lasts until the weather warms up, but if it goes out completely, what happens if I replace the pump and don't wait 24 hours before starting up the system? My concern is that the PVC glue won't have adequate time to set.