power needed for Pentair easy touch 4

rascal63

Silver Supporter
Dec 27, 2019
15
Galt, Ca
Hi, I have just mounted an ez4 panel. Nothing cut over to it yet. Right now I have a:
12v amerlite pool light,
pool pump(older single stage) ,
waterfall pump,
and a natural gas heater (not working) . will be upgrading soon to a pentair natural gas heater.
These are all run thru an intermatic timer. Pool pump only thing on timer with pressure side auto cleaner off 25% of pool pump valve. Everything else on switches with GFCI for light. All these accessories currently come from house on their on breakers thru Timer box ( looks like spaghetti).
Pool is in ground gunite kidney shaped 30 year old pool and seems all is 30 years old except for pump replacements.
Question 1 is: what size breaker will I need for the equipment listed at the new easy touch 4 control box?
I was hoping to get a way with a double pole 40 amp circuit breaker.
I currently have an existing 3/4" conduit that has all the wires for existing equipment from house.
This is my own pool and the picture below shows what I have now. (and yes, the previous owner/pool guy actually wired the pool pump straight into cabinet-cannot close door) all conductors from house panel come up thru 3/4" conduit into gfci box. I hope this makes sense to someone. Any help greatly appreciated, Russ
 

Attachments

  • 20191216_195047.jpg
    20191216_195047.jpg
    377 KB · Views: 13
Welcome to TFP.

40 amps should work to feed your ET. You should not load CB more than 80% so maximum load should be 32 amps or less.

You need four #8 copper wires from the CB to the ET panel - 2 black hots, white neutral, and green ground wire. It may be a tight pull in 3/4” conduit.
 
Welcome to TFP.

40 amps should work to feed your ET. You should not load CB more than 80% so maximum load should be 32 amps or less.

You need four #8 copper wires from the CB to the ET panel - 2 black hots, white neutral, and green ground wire. It may be a tight pull in 3/4” conduit.
I Thank you so much for your quick response. I forgot to ask is it possible to drive new ground rod at pad and ground to that and just run 2 hots and neutral? Thanks again for such a quick response and I really appreciate your time. If not , I will just get a big jug of pull soap and hope for best. Thanks again, Russ
 
I Thank you so much for your quick response. I forgot to ask is it possible to drive new ground rod at pad and ground to that and just run 2 hots and neutral?

No. Code and good electrical practice requires one ground point for the house electrical system. All subpanels must be grounded back to the main panel.
 