  1. swamprat69

    Pentair MiniMax Plus 400 - Pilot light works, burners don't fire

    It looks like the corroded connection is the MV (main valve power) connection. PV=pilot valve power and MV/PV= common power connection. It looks like the male spade connection at the gas valve is corroded off. Due to the excessive corrosion of the gas valve, just replacing the gas valve may not...
  2. swamprat69

    Hayward Heater - Gas Valve - Why Do These Fail?

    If the gas valve solenoid is sticking closed when voltage is applied, you will draw more amperage than the listed amps on the gas valve label and might blow a low voltage fuse. If the solenoid coil is open, you will show 0 amps when the gas valve is powered.
  3. swamprat69

    Flooded heater - safe to try and turn on or no?

    If it did submerge the heater I would also include any and all electronics, safeties and wiring connections. Feel free to ask any questions of our experts here regarding a new heater.
  4. swamprat69

    Flooded heater - safe to try and turn on or no?

    If the water level reached the height of the rust on the outside of the AC condenser it is likely that the gas valve, inline regulator and some heater safeties were in the water and these should be replaced in order to run the heater safely. This is true even if these parts were only partially...
  5. swamprat69

    Raypak Electric Heater “Comp Start Delay

    Regarding the high-pressure trip/lockout, the water flowing through the heat pump from your pool is what reduces both the pressure and temperature of the discharge gas from your compressor and causes it to condense into a liquid transferring the heat to your pool water. Low water flow from a...
  6. swamprat69

    MasterTemp AFS Error

    If your heater is running the AFS contacts are part of an electrical circuit and you would be measuring voltage not resistance. If the blower is not creating adequate differential pressure either to close the AFS contacts or keep the AFS contacts closed, there can be numerous causes for that.
  7. swamprat69

    MasterTemp AFS Error

    There are only 2 choices when you have an airflow switch problem. Either you are developing the correct pressure differential to make the switch close and it isn't closing (failed airflow switch) or you are not developing the correct pressure differential to close the switch. A differential...
  8. swamprat69

    Ray pac 266a heat exchanger issue.

    Difficult to tell without seeing all of the parts both inside and outside of the burner compartment, but from the excessive amount of corrosion it might not be due to a water leak from the heat exchanger/water manifold. You could try running the heater with the gas supply shut off to see if you...
  9. swamprat69

    kool deck resurfacing

    I used Craftsman Coatings Inc 1625 Athol Ave, Henderson, NV 89011 (702) 829-8135 they are a concrete contractor
  10. swamprat69

    kool deck resurfacing

    Ended up getting all of the old removed, etched, rinsed, coated and colored. and then sealed for $ 3000 (just under $6/sq,ft. Crew was very detail oriented and left everything very clean. Looks great! I might have them clean, stain and seal my concrete patio next.
  11. swamprat69

    kool deck resurfacing

    I have a 20-year-old pool with a type of cool deck in Las Vegas. The decking was showing wear and deterioration. During covid I had a company attempt to do a repair and it turned out badly. The parts that they repaired looked good for about a year, but are now showing ugly wear in the repaired...
  12. swamprat69

    Help diagnosing Jandy LXI heater, Ignition fault error, Fenwal air flow fault with single blink red LED

    So you are saying that the "IGN/FS" and the "PS" wires are switched at the Fenwal? In that case you would be putting 24V from the closed contacts of the pressure switch to the flame sensor circuit which is not active until the end of the sequence of operation when the Fenwal checks for flame...
  13. swamprat69

    Help diagnosing Jandy LXI heater, Ignition fault error, Fenwal air flow fault with single blink red LED

    You said that you get a 1 blink fault code at the Fenwal. That is an airflow fault code and you would not start the ignition sequence by putting 24V to "PS" on the Fenwal and powering the ignitor for the 40 sec warmup nor get 24V between "VAL" and "GND" after the warmup.
  14. swamprat69

    Help diagnosing Jandy LXI heater, Ignition fault error, Fenwal air flow fault with single blink red LED

    How did you test the airflow switch? With a differential manometer? If the blower starts up, you should have 24V between "W" and "GND" on the Fenwal. If you then don't have 24V between "PS" and "GND" on the Fenwal, either the pressure switch is not closing because of insufficient airflow (...
  15. swamprat69

    Hayward h-series low nox pool heater - Gas

    You are showing both sides of the connections for the 2 wires (at the connector for the "fuse circuit board" and the "control module"). It appears to be burnt off at the 2 pin connector to the "fuse circuit board". The fuse circuit board part number should be FDXLFWP1930. The 2 wires are the low...
  16. swamprat69

    Hayward Heat Pro Issue

    If it is a weak or open compressor capacitor it should be warrantied by Hayward. Out of curiosity, how old is the heat pump, who did you purchase it from and who installed the heat pump?
  17. swamprat69

    Hayward Heat Pro Issue

    You should also check that the compressor capacitor is within + or - 10% of the listed MF rating.
  18. swamprat69

    Relay jumper disintegrated on Balboa VS500 board - advice?

    Discoloration of the HTR2 connection at the circuit board is an indication of a poor/loose connection which would cause increased resistance and high heat at that point.
  19. swamprat69

    Raypak heater burner tray is collapsed- pool company pushing for replacement

    As I meantioned before, there is a very high probability that the damage extends beyond just the burner tray. Attempting repair by someone who is not thoroughly trained in ALL safety precautions needed to make the repair competently would be a big mistake and might result in a hazardous condition.
  20. swamprat69

    Jandy JXI400 Heater No Power

    That will still not address the core issue. It would appear that you have a direct short to ground on the low voltage side of the transformer. You will need to track the short to ground down or you will just keep blowing fuses instead of the transformer.
  21. swamprat69

    Jandy JXI400 Heater No Power

    It should be a 2 Amp fast blow glass fuse. Most fast blow glass fuses have a small thin wire inside. Slow blow fuses have either a coiled wire or a flattened ribbon wire and are meant to blow only under a sustained overcurrent load. If you have larger than a 2 Amp fuse or a slow blow fuse, you...
  22. swamprat69

    Jandy JXI400 Heater No Power

    When you replaced the fuse was it an exact match for the one that as blown? That fuse is the protection for the transformer.
  23. swamprat69

    Pool Heater part needed

    Tried to google as Pentair 471424. While most on the list showed as discontinued or out of stock, you might try contacting those that do not show the part as such. Someone may have one sitting around.
  24. swamprat69

    AqualCal heater fan motor replacement

    Most fan motors can be replaced with non OEM motors as long as the specifications match. A photo of the fan motor and its label is needed to confirm that. Some manufacturers attempt to make it difficult to replace by using OEM fan motor connectors or OEM fan motor mounts or non traditional shaft...
  25. swamprat69

    HP31005T reverse heating and cooling

    Heat pump reversing (4 way) valve wired incorrectly or incorrect reversing valve. When the reversing valve is powered it shifts in one direction and when it is not powered it shifts in the other direction. The valves could be either powered for heating or powered for cooling, depending on the...
  26. swamprat69

    CSI and tile water line calcium buildup

    I can see that CSI would need to be extremely negative and PH would probably kill my heater.
  27. swamprat69

    CSI and tile water line calcium buildup

    Recently had a failure of autofill valve and noticed it had popped up and overfilled the pool. Pool filled to within an inch of the top of the skimmer. Reseated autofill at a lower level and shut off autofill feed. With the pool level above the accumulation at the tile waterline can I try to...
  28. swamprat69

    Heater Inverter showing "High Pressure" Alarm? Ideas?

    At least any parts needed should still be under warranty
  29. swamprat69

    Heater Inverter showing "High Pressure" Alarm? Ideas?

    Should still be under warranty for both parts and labor then. Just make sure that the heater is running 100% before the one year covered labor expires.
  30. swamprat69

    Heater Inverter showing "High Pressure" Alarm? Ideas?

    Good idea... looked at your user guide and it doesn't really give any technical information.