    STA-RITE SR400HD Will not stay on. SOLVED !!

    Problem Solved !! Thank yo to James and everyone else !! Plumber tested the blew and tested lines, they were clean and no leaks. Next he checked the pressure coming from grid, which has dropped to 1 PSI. We called Gas company and they came in and changed the meter and regulator and a bunch of...
  2. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Yes we do, it's the main for the backyard (BBQ and Pool) we shut it off whenever we close the pool for the season. It's fully open.
  3. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Thanks, already called my gas contractor (the one who installed the line) will be here in tomorrow morning. I will post here once we find out the issue, so hopefully it will help someone else. Thanks for all your help !!
  4. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    I am guessing we found the issue? I am getting 6.17 when off, and -1.28 when calling for heat. What could cuase pressure to drop in a gas line? we installed this gas line about 6 years ago and was working fine until last season.
  5. 2020-06-04 16.44.20.jpg

    2020-06-04 16.44.20.jpg

  6. 2020-06-04 16.43.58.jpg

    2020-06-04 16.43.58.jpg

  7. 2020-06-04 16.44.20.jpg

    2020-06-04 16.44.20.jpg

    Gas on
  8. 2020-06-04 16.43.58.jpg

    2020-06-04 16.43.58.jpg

    Gas off
  9. Issac

    Issac

    Pool Stuff
  10. 2020-06-04 16.43.58.jpg

    2020-06-04 16.43.58.jpg

    Gas Pressure off
  11. 2020-06-04 16.44.20.jpg

    2020-06-04 16.44.20.jpg

    Gas Pressure on
  12. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Thanks again James ! Ordered this Manometer, gas cut off valve is inches away, looks simple enough to try. Thank You!
  13. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    I played around with the new ground wire location and now I am getting solid 2.5 - 2.6, and within 10 seconds it starts dropping slowly and shuts off when reaches 0.3 - 0.4. I checked continuity of ground points earlier, didn't pay attention to ohms resistance, what number am looking for...
  14. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Hi James, I tested the current between the FC +/- and it fluctuate between 0.50 and little over 2, mostly it stays below the 1.0. Is there a way to test if I did the extra ground correctly?
  15. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    I have added the extra ground wire, tried both locations, still same issue. I don't have a True RMS Multimeter to test FC+/-. Can you please tell me if either will work? https://www.amazon.com/dp/B07VNFVDW8 https://www.amazon.com/dp/B07P7V3YNT
  16. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Thank you James, I will add the ground wire today before trying anything else.
  17. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    The igniter did not do the trick for me. I called Pentair support and was told to try to run the unit without the thermal regulator (which I tested before with hot water and it looks fine). He said if the unit still fires up and shut down in a cycle like it does, to check on the Manifold bypass...
  18. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Thank you! I will order the igniter and go over the ground wires once again, hopefully will not need to change the Ignition control. I will report back once I replace the igniter. Thank You!!
  19. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Any other suggestion? Is it possible one of sensors like the AGS is melfanctioing and we are not getting an LED light indicating ?
  20. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    I am getting 26V when not calling for heat, and 25V when calling for heat. Never goes out completely.
  21. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Thanks, will give it a try. .
  22. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Yes, I do have a multimeter.
  23. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    When it comes on for about a minute, I do get hot air from the exhaust vent, both my valves are on, first one will turn on the bbq and pool, second one is right next to the heater. LED comes on for less than a second when I turn it on, but noting when heat goes off. I don't think it's the...
  24. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Allen, There are no blinking lights on the Fenwal, the LED comes on briefly when I call for heat and the device comes on. But nothing when the heat stops. Also went over all wires and clean some of the connections with a steel brush. The heater stays on for about a minute before stopping, so I...
  25. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Thanks Allen, I will check the LED's on the Fenwal later on today, I suspect it's something with the wiring, I will clean up with a steel brush on all contacts. Thanks Kevin, I believe my water pressure is fine, although I don't have a tool to measure, all preasure out of the returns and...
  26. I

    STA-RITE SR400HD Will not stay on. SOLVED !!

    Hello, I have a 2013 Pantair STA-RITE SR400HD that will not stay on. Everything looks fine, temperature showing correctly, it starts up normally, first blower comes on, about 30 seconds later the burner comes on. Burner stays on for about a minute and and stops, about half a minute to a minute...