Aqua logic goes into service mode on its own.

The aqua logic control panel was in direct sunlight, but is now shaded. It ran overnight but at some point,, it went into service mode on its own again. I took it out of service mode, and it started up again, but not confident it won't go back into service mode later as the temperature gets warmer, high of 115 today.
 
Sorry - I assumed with a Pentair pump you had Pentair automation.

Not sure why the Hayward system would do that. It is fairly old.
 
Possibly a failing control board.

How old is the box?

What is the serial number from the inside of the door?

What is the model number?

Do you have pictures of everything?
 
Model # AQL-PS8
Serial # 5L0602-1013322
After shading the control panel for several days, the problem seems to be rectified. The pump ran all night and all day yesterday with no issues. I can only assume being exposed to 118 degree temp was a factor.
 