    Pentair Mastertemp 400 already replaced SFS and still getting E05

    When you say wires, are you referring to any specific wires that might be damaged? SFS wires/control board wires/or all wires?
  2. E

    Pentair Mastertemp 400 already replaced SFS and still getting E05

    Thank you so much! I will report back : )
  3. E

    Pentair Mastertemp 400 already replaced SFS and still getting E05

    E05 comes on after the heater starts (about 10-20 seconds after the hot exhaust kicks on) and when I hold down the "pool on" button, it stays on 80, then flashes to 40, then back to 80. We just replaced the stack flue sensor yesterday.
  4. E

    Pentair Mastertemp 400 already replaced SFS and still getting E05

    We are having the same problem many have posted about - start up heater, once the ignition kicks in, it blows hot for 10 -20 seconds, then turns off and displays E05. On the control board, the SFS light is lit along with LED11 (service heater). We replaced the SFS yesterday and still get this...