Hayward H250 16 years old……. Solid service light- blinking LO error…..

Nashvillejoe

Gold Supporter
Apr 14, 2013
119
Nashville
Pool Size
20000
Surface
Vinyl
Chlorine
Salt Water Generator
SWG Type
Hayward Aqua Rite (T-15)
So i havent used my heater in about a 8 mo- last year i installed a new heat exchanger and used it for most of 2021. By the end of the year we decided to refurbish the pool so i didn’t use the pool or heater over the winter months….. finished refurbishing the pool and and tried to fire up the heater and i get the solid service light and the blinking LO….

I do have a sensor issue in the call Omni logic app no flow- could that be causing my heater to not working- my sense is no - that error is most likely from me shutting the system down to swap the T15 and filters(?)

as i said the exchanger is about a year old and i have a TriStar Variable so i know i am getting plenty of water, the exchanger is new and i can control my heater from the OmniLogic app……

My first thought …… is there a way to reset the panel?? (When i power off the heater- my pump stops and then will restart….. so that sensor is functioning..

What is best way to isolate the sensor that is causing the fault…..

thanks in advance!!
 

Attachments

  • 620FDF68-DBBD-4F29-9A70-28ECC2E1B122.jpeg
    620FDF68-DBBD-4F29-9A70-28ECC2E1B122.jpeg
    42.5 KB · Views: 4
Last edited:
LO seems to be the pressure switch, increase speed on the heater circuit. Clean the filter if necessary.

New filters installed yesterday and running a Tristar at 90% - is it and instantaneous reading - maybe the flow sensor is corroded - can I bypass the circuit and just tie the two sensor wires ??
 
All pressure switches are fairly similar usually you can see the piston open will the pump is on and it hits the microswitch to close the loop. You can bypass it but it should only be done for testing.
I was only going to use it for testing after reading some of the threads I’m thinking it’s probably just time to buy a new heater5C920D2B-4AAB-4D94-9453-3A1FCB482B43.jpeg
 
The pressure switch looks like it’s behind front panel. You can also flush tubing and try cleaning pressure switch if it’s not opening. Don’t adjust it though. Instead of jumping it you can use a flat head and engage microswitch on the pressure switch. If the microswitch is bad it will have to be jumped or tested.
 

Attachments

  • E7E12C79-2C78-4E69-883B-59775957D0A0.png
    E7E12C79-2C78-4E69-883B-59775957D0A0.png
    204 KB · Views: 11
Last edited:
Okay so i clipped the wires and bypassed both sensors and the unit fired right up - working perfectly

so does anyone know what sensors those are - i figured i would just replace them both



C956A834-652C-4744-8F97-605BE0713DE3.jpeg
 
View attachment 416838View attachment 416839
Best to verify with your manual but that came up as Hayward’s h250 manual. Hls 135 hls 160. It’s best to jump the quick disconnect terminals with a wire instead of cutting wire.
I think I found the culprit - its that white sensor…… interesting though….. i thought there was a flow sensor that opened and closed with the flow…. And everything i pulled off the manifold is just pieces that have no mechanism to affect flow- it seems like most of the holes are filled with caps….… i am guessing that one pressure switch is it
 

Attachments

  • B3659454-EB25-41B9-B4E9-076811528556.jpeg
    B3659454-EB25-41B9-B4E9-076811528556.jpeg
    300.3 KB · Views: 8
  • 6257FB48-7E72-418C-B582-BA5D768216A7.jpeg
    6257FB48-7E72-418C-B582-BA5D768216A7.jpeg
    271.8 KB · Views: 6
  • BD53EE9B-92C4-4DDE-92C2-C19DE2AC7C19.jpeg
    BD53EE9B-92C4-4DDE-92C2-C19DE2AC7C19.jpeg
    267.6 KB · Views: 8
  • 4CD564B3-9B0C-4CA0-8500-3D90873F0D7D.jpeg
    4CD564B3-9B0C-4CA0-8500-3D90873F0D7D.jpeg
    266.5 KB · Views: 9
  • 0944AA9D-FA2F-468A-9B70-C091A8128C80.jpeg
    0944AA9D-FA2F-468A-9B70-C091A8128C80.jpeg
    268.5 KB · Views: 9

Enjoying this content?

Support TFP with a donation.

Give Support
I think I found the culprit - its that white sensor…… interesting though….. i thought there was a flow sensor that opened and closed with the flow…. And everything i pulled off the manifold is just pieces that have no mechanism to affect flow… i am guessing that one pressure switch is it
That is a pressure switch not a flow sensor.
 
i don’t see a flow sensor anywhere on my heater…… i do see one in my piping after the salt cell - is it possible there is supposed to be a flow sensor on this and the previous owner removed it and replaced it with a cap ??
 
This is the only mechanical attached to the manifold and as you noted its clearly a pressure switch!!
 

Attachments

  • 69EE3364-67C0-4B0E-9B1C-2CFD2063267F.jpeg
    69EE3364-67C0-4B0E-9B1C-2CFD2063267F.jpeg
    291.8 KB · Views: 6
The no flow on the Omni logic is probably related to your salt system. Your omnilogic doesn’t communicate with the heater in that way. It only tells the heater to turn on or off based on the omnis temp sensors and demand. LO is a pressure issue, not exactly sure why it would fire with hls bypassed.
 
The no flow on the Omni logic is probably related to your salt system. Your omnilogic doesn’t communicate with the heater in that way. It only tells the heater to turn on or off based on the omnis temp sensors and demand. LO is a pressure issue, not exactly sure why it would fire with hls bypassed.
If the relay on the pressure switch is shot- than it wont complete the circuit so even though there is sufficient pressure- the relay will read- no pressure-

so i will swap out that part and i would bet a nickel i will be good to go !!!

thanks so much for helping - i will post the resolution after i track down that part
 
  • Like
Reactions: Poolbreh
These hi limit switches have a fair amount of copper oxidation on them….. at first i thought it was some kind of copper plating and then i realized its most likely oxidation so just wanted to confirm before i took steel wool to the base and cleaned off the oxidation


433A035C-6F27-490D-B004-C1060DA4564F.jpeg
 
I don't think the oxidation has any impact on their functioning. The electrical contacts need to be clean and the temperature controlled switch is all internal to the sensor.
 
LO is a limit string so it checks the loop of multiple sensors before firing. One of those hls must of been open upon LO test that’s probably why it fired. If the pressure switch engages microswitch, I would jump or test each hls individually one of them is open. For future reference don’t cut the wire just use the quick disconnects and bridge with a small piece of wire.
 

Enjoying this content?

Support TFP with a donation.

Give Support
Thread Status
Hello , This thread has been inactive for over 60 days. New postings here are unlikely to be seen or responded to by other members. For better visibility, consider Starting A New Thread.