I measured about 235 volts so 240V is the factory default, unless they messed up the install, I’ll take a look under the coverThe Intelliflo takes 240 volts.
Where exactly does the heater get its power from?
Is there a separate breaker or switch?
You can test it if you are comfortable doing that.
If I recall correctly, you should be able to measure 50 ohms across the igniter. If it shows open, then the igniter is broken.Are you smelling gas?
Are you getting any ignition at all?
If no ignition, then it might be a bad ignitor.
Check to see if the igniter is getting voltage or check to see if the ignitor is drawing about 5 amps.
They made all those crazy elbows to add a union and shutoff valve, I know. Brutal design…Wow … 7” WC into the house, that’s really low. Residential NG pressure on the low side should go all the way up to 14” max. I suspect the regulator is either undersized or bad. The street pressure is 2 psi. Then the regulator takes it down to low pressure BUT the regulator also needs to be spec’d for both pressure AND FLOW. If the regulator is too restrictive then you won’t get enough gas to the heater.
Also, whoever put the gas pipe for the pool that close to regulator and then did all that piping to go around the vent was not to bright. Maybe ask the gas service tech if it’s possible to clean that installation up. Lots of unnecessary 90’s.
Also, so I know what to ask the gas guy, I understand the pressure part of the regulator, but how does it effect flow, as in is their an adjustment for that or just a larger regulator?Wow … 7” WC into the house, that’s really low. Residential NG pressure on the low side should go all the way up to 14” max. I suspect the regulator is either undersized or bad. The street pressure is 2 psi. Then the regulator takes it down to low pressure BUT the regulator also needs to be spec’d for both pressure AND FLOW. If the regulator is too restrictive then you won’t get enough gas to the heater.
Also, whoever put the gas pipe for the pool that close to regulator and then did all that piping to go around the vent was not to bright. Maybe ask the gas service tech if it’s possible to clean that installation up. Lots of unnecessary 90’s.
Also, so I know what to ask the gas guy, I understand the pressure part of the regulator, but how does it effect flow, as in is their an adjustment for that or just a larger regulator?
Does this mean the Max pressure out of the regulator would be 8.5”WC, maybe that a SoCal gas restriction?Regulators are designed to stabilize/reduce pressure from the inlet to the outlet. This is done with a set of diaphragms and internal springs to produce the correct pressure drop. That being said, the internal orifice sizes are fixed and can only allow a certain flow rate for a given pressure drop. Typically, the “larger” the regulator (as measured by its diaphragm diameter) the higher the flow rate of gas for a fixed pressure drop.
So all you need to do is make sure that the regulator and meter they install gives you the maximum allowable static pressure (according to local residential codes and whatever limitations the gas company has in place) and that it designed for a flow rate that exceeds all of the requirements of your various appliances. A 400kBTU/hr heater needs 400 cubic feet of gas per hour. Your hot water heaters are typically a lot less than that as are range tops. Even so, the meter and regulator should be spec’d to deliver all the gas you could reasonably need.
So 8.0" can be ok;8" wc should be sufficient.
Below shows that at a starting static pressure of 8" wc and a drop of 3", the capacity is 1065 CFH.
This means that if the pressure is 8" at the meter, the pressure at the heater would be at least 5" wc during operation.
As long as the static and dynamic are within the range of 4" wc min to 14" wc max, the pressure should be fine.
View attachment 414203
Also, note that the heater should have a drip leg, which your does not.
View attachment 414204
View attachment 414205
View attachment 414206