I would run your main pool feed the other way into the Main Lug Sub-Panel. How many amps will be the pool panel feed?
Put an 80-100 amp CB into the sub panel feeding the intelliCenter.
Put your landscape light breakers into the subpanel.
One of the advantages of this is the breaker in the subpanel is the disconnect for all the high voltage in the IntelliCnter. It makes it very convenient if you are making any wiring changes in the IntelliCnter to just reach over and flip the breaker instead of a trip to the house main panel.
This then frees up two 240V GFCI 20A breaker positions for your spa pumps.
Also consider installing a surge suppressor in the subpanel which will require another 240V CB in it.
www.troublefreepool.com
Put an 80-100 amp CB into the sub panel feeding the intelliCenter.
Put your landscape light breakers into the subpanel.
One of the advantages of this is the breaker in the subpanel is the disconnect for all the high voltage in the IntelliCnter. It makes it very convenient if you are making any wiring changes in the IntelliCnter to just reach over and flip the breaker instead of a trip to the house main panel.
This then frees up two 240V GFCI 20A breaker positions for your spa pumps.
Also consider installing a surge suppressor in the subpanel which will require another 240V CB in it.