Recent content by adam2817

  1. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    FIXED! The breaker was the problem. But when I took the top circuit board off, I reversed the 4 pin connector when putting it back together. Corrected the polarity and Boom! everything came on. Thanks so much for the assistance along the way! You saved me a ton of money! Thanks! Ajw22
  2. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    This is where I'm at this afternoon. Breaker replaced. 240 at both poles at breaker. 240 at the end of the run. 240 across to L1 and L2 at pump. As shown. Still nothing. I do hear some clicks at the pump. Which is more than I got before
  3. 20221006_142653.jpg

    20221006_142653.jpg

  4. 20221006_142432.jpg

    20221006_142432.jpg

  5. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    I do have 240 at the breaker now.
  6. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    Well, I thought we were on to something. And we may have fixed some of the problem, however I am still not getting power to the pump.
  7. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    It used to feed a Pool Heater, but that is not here. I am going to replace it with a 30A 220, so I can use.my henerator to backfeed a few lines when the power goes out again. But as of now, it feeds nothing. And everything else in this house is a bit ratty. 3 months new to my family and here we...
  8. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    This is what I got. I tested the black and red feeds into the breaker panel. Got 240. I tested across the breaker and got a weird reading. As seen in the attached photo. I'm beginning to think you guys are on to something. Like a bad breaker.
  9. 20221005_170708.jpg

    20221005_170708.jpg

  10. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    I Do not have an on call.
  11. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    Volt meter. At the breaker box. Probe to one side of the breaker and One to ground. I test both poles the same way. Then I test at the pump end. Each are measuring 120v. Probe to wire and probe to ground. When I go across from 120v line to 120v line (L1 and L2) I do not get 240v I also don't see...
  12. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    I do NOT have 220 between both poles.
  13. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    Yes, I checked with a meter. 110/1120 at each pole.
  14. A

    Hayward Max-flo VS SP2300ZLV NO POWER

    we just got done with Hurricane Ian and prior, I turned off the breaker to the pool just in case we got water, it wouldnt burn out and short the pump. Home now, turned on the breaker and nothing. No display. I checked that I have power to the motor and I have power. Motor is doing nothing...