spa heat maxes out at pool setting or (95).

Skell

Member
Mar 3, 2024
22
Cape Coral FL
Pool Size
24000
Surface
Plaster
Chlorine
Salt Water Generator
SWG Type
Hayward Aqua Rite (T-9)
spa heat maxes out at pool setting or (95). If I change the heat setting for the pool it stops at what ever the pool heat is set for. Hayward HeatPro Heat Pump HP21404T, 24000 GAL CONCRETE POOL,
PENTAIR INTELLIFLO3 PUMP, PENTAIR EASYTOUCH CONTROL SYSTEM, AQUARITE CHLORINE GENERATOR
new filter pump and controls just installed Heat pump was working OK with old RS4 controls. Pool dude says I need a
new heat pump for another $6000. I think he wired something wrong and he thinks I am an easy touch because I am old.
 
Last edited:
On the heat pump the temp on the spa is set to 104 and pool is set to 95 (defaults).

Raise both of those to the maximum. But it sounds like the heater is never getting the signal that the spa is on and staying on pool heat.
 
But it sounds like the heater is never getting the signal that the spa is on and staying on pool heat.

The EasyTouch does not give any signal with the firemans switch connection.

Both the pool and spa heat with the HP POOL temperature setpoint. Put it up to 104.
 
The EasyTouch does not give any signal with the firemans switch connection.

Both the pool and spa heat with the HP POOL temperature setpoint. Put it up to 104.
The EasyTouch does not give any signal with the firemans switch connection.

Both the pool and spa heat with the HP POOL temperature setpoint. Put it up to 104.

The EasyTouch does not give any signal with the firemans switch connection.

Both the pool and spa heat with the HP POOL temperature setpoint. Put it up to 104.
HP POOL temperature setpoint can not be set above 95
 

Enjoying this content?

Support TFP with a donation.

Give Support
HP POOL temperature setpoint can not be set above 95

Hayward is terrible with their HP manuals. You need to get the heater to run in SPA mode.

Which of these pages apply to your HP?


1717882370266.png

1717882393370.png
 
How
Raise both of those to the maximum. But it sounds like the heater is never getting the signal that the spa is on and staying on pool heat.
It heats the spa up to the temp that the pool is set to and maintAINS IT there. It is getting the signalthat the spa is on,just will not go above the pool setting.
 
How

It heats the spa up to the temp that the pool is set to and maintAINS IT there. It is getting the signalthat the spa is on,just will not go above the pool setting.

Sounds like Allan covered this above. The heater is not in spa mode.
 
H P can not be set above 95 for pool and spa is set for 104

Ohhhhhhh K ..... Are you using the fireman's switch to control the HP? If so, the heat pump needs to be nailed into SPA mode. The HP doesn't know if it is needed for the pool or the spa so needs to be forced to spa only. That is what the above directions say to do.
 