  1. swamprat69

    Heaters and flow

    A higher flow rate would definitely increase the heat transfer coefficient, but the increase would not be proportional. The increase in the heat transfer coefficient would be minimal ( mid to low single digit percentage rise at most) and would entail a higher cost for running the pump at a...
  2. swamprat69

    Problem with heater

    It is entirely possible that the problem is not with the gas valve, so I would first try to get a qualified technician to do a throrough clean and check on the heater. I know that this can be difficult as most HVAC techncians won't work on pool heaters and most technicians that do work on pool...
  3. swamprat69

    Problem with heater

    Both K and H in the 7th digit designate a slow opening gas valve, You could go with a competitors valve that crosses to your original honeywell valve model number, but the physical pilot and electrical connections may require you to make some adaptations. Page 2 shows model specifications
  4. swamprat69

    Problem with heater

    Your heater does not look like it has been cleaned and operation checked by a qualified technician in a while. This can effect its operation in various ways. Let me know if this assumption is not correct. The valve that you are showing is not a replacement for the valve that is shown in your...
  5. swamprat69

    Jandy JXI heater wont ignite in evening

    When the heater fails to fire up, are you getting any diagnostic codes flashing on the red indicater light on the Fenwal ignition control?
  6. swamprat69

    Pool Heater Broke Following Lightning Event

    Took a quick look and I am having a problem following what should be a logical troubleshooting process. Trying to troubleshoot 2 interconnected systems without isolating them from each other would be frustrating ( did see that you jumpered firemans switch, removing easytouch from the heater)...
  7. swamprat69

    What are these jumpered connectors on the outside of my Jandy Laars LT400N-L heater?

    Those 2 receptacles are wired in series. Obviously the wire jumpered around both switches that the receptacles were plugged in to. From looking at the wiring diagram, there is a good chance that they are the high limit switches ( safeties that prevent the heater from overheating ). The heater...
  8. swamprat69

    Hayward H400 manifold spacing

    How old is your heater? Has it ever been cleaned by a qualified technician? The "air box" is meant to be sealed (that is why it has a gasket). The heater was designed and approved to operate as it came in the box. There could be many different things (parameters) that could cause your symptoms...
  9. swamprat69

    Raypak 206a pilot light intermittently staying on

    The common terminal on the gas valve should be labeled either "C" or "MV/PV" ( Robertshaw or Honeywell ). If you have 24V between ( C or MV/PV ) and PV then the problem is with the control board. If there is no 24V between ( C or MV/PV ) and PV when the pilot is lit, then the pilot solenoid in...
  10. swamprat69

    Pentair mastertemp troubleshooting

    Ignitor warm up is 20 sec.. Trial for ignition is 7 sec. and that is when the gas valve should be powered on. This should be the manual for the heater https://images.inyopools.com/cloud/documents/pentair-heater-mastertemp.pdf The connection and ladder diagrams should be on pages 36 & 37...
  11. swamprat69

    CO2 Heat pump for pool.

    Eco???? CO2 in the atmosphere is a major cause of global warming!
  12. swamprat69

    CO2 Heat pump for pool.

    Looks like you have to use their holding tank with the heat pump. Water connections at the heat pump are 1/2" NPT. Water connections at the holding tank are 3/4" NPT. Recovery is listed at roughly 20 GPH. At optimal conditions it would raise your 7.5K pool water about 1 degree evry 4 Hrs..
  13. swamprat69

    CO2 Heat pump for pool.

    It only puts out 15,400 BTUs/hour...way too small!
  14. swamprat69

    Hayward H200 Ignition failure code

    Heating mode:The control continually compares the water temperature with the set point and the high limit temperature. When the water temperature is more than 1° below the set point a call for heat is generated and a heating cycle is initiated.1. The control checks for open contacts at the...
  15. swamprat69

    Hayward H200 Ignition failure code

    Trial for ignition in which the gas valve is powered is 4 seconds! The gas valve is not a 2 stage opening valve, but a dual seated valve ( "VR" on Honeywell ) with standard opening ( "M" on Honeywell). Troubleshoot normally by assuming there is no ignition during the 4 second trial for ignition...
  16. swamprat69

    Sta-Rite SR400NA Heater Blowing Fuses

    TYVM and tell your father in law WELCOME HOME
  17. swamprat69

    Sta-Rite SR400NA Heater Blowing Fuses

    P.S. Also make sure that all wiring connections stated above are dirt and corrosion free.
  18. swamprat69

    Sta-Rite SR400NA Heater Blowing Fuses

    Not sure what electrical meters you have? Basic multimeter? Clamp type ammeter? Sequence of operation goes... 24V in to IND on the fenwal starts the blower if the water pressure switch and high limit switch are closed... Then when the air pressure switch closes, you get 24V to TH on the fenwal...
  19. swamprat69

    Hayward Heat Pump FLO Error

    With the pump off you should measure 24V across the purple wires and with the pump on you should measure 0V across the purple wires.
  20. swamprat69

    Hayward Heat Pump FLO Error

    This should be the installation (owners manual?) guide for your heat pump as I dont know whether you were only left the users guide which won't do a lot of good in serious troubleshooting as it has no wiring diagram Hayward HeatPro Heat Pump | Heat Pro. Page 11 has a wiring diagram, but no...
  21. swamprat69

    reinserting eyeball

    TYVM
  22. swamprat69

    reinserting eyeball

    What tool do I need to put this eyeball back in? No markings at all, but it is a horizontal jet in the pool and my popups are A&A
  23. IMG_1828.jpg

    IMG_1828.jpg

  24. swamprat69

    Pentair Master Temp Gas Valve Buzz

    It might also be helpful to measure the amp draw of the gas valve and check it against the amp rating on the gas valve.
  25. swamprat69

    Pentair Master Temp Gas Valve Buzz

    Most likely causes for a buzzing/chattering gas valve would be low/marginal voltage needed to operate the gas valve, worn/defective solenoid valve(s) that are not pulling in correctly or voltage dropping under load. Suggest pulling the 2 yelow wires off the gas valve and measuring voltage at the...
  26. swamprat69

    MiniMax Nt 400 control board dead

    You might also want to check the blower motor capacitor to see if it is within + or - 10% of its rating as it might not be coming up to speed. Also check the fins/vanes on the blower wheel as Poolbreh suggested.
  27. swamprat69

    venturi size

    Attempting to mod a pilot orifice is not a good idea. Just replace the pilot assembly.
  28. swamprat69

    Jandy JXI 400N Makes a Whining Sound When Heating

    Still no signature filled out for pool. Other than previously noted potential problems, venting may also be too close to window and exhaust may cause deterioration of AC/HP condenser coil. Is the heater installed in a mudroom? No idea of where pool is situated in relation to the exhaust and...
  29. swamprat69

    MiniMax Nt 400 control board dead

    Does this look like the manual for your heater? https://www.tiledspas.com/images/Other/Heaters/MiniMax_NT_man.pdf You say that you have no lights, but have 24V at the board. Are you measuring 24V at the P4 connection to the board? If so, are you also able to measure 24Vbetween the "24VAC"...
  30. swamprat69

    Jandy JXI 400N Makes a Whining Sound When Heating

    Direct sidewall venting for the heater is not correct. Exhaust should not be elbowed down towards the ground (also clearance to ground/snow). Intake (combustion air) and exhaust should exit at the same height (exhaust byproducts are hot and tend to rise and if exhaust is lower than intake for...