Recent content by CMarsh

  1. C

    Intelliflo VSF pump won't run when connected to automation via iAqualink

    Photos attached of power center and relay 1 (filter pump). An explanation here may be warranted, as the electrician who installed this in 2018 put in a GFCI (photo 1 lower left) that effectively serves as a breaker for the Jandy control and AquaRite SWG elements. Additionally he wired in a...
  2. C

    Intelliflo VSF pump won't run when connected to automation via iAqualink

    Hi. I labeled the aux socket pins as I removed them and reset them in the new PCB. I just went out and followed the wires to visually confirm that the pump is indeed in the first slot, with the cleaner in the adjacent spot. I confirmed that all the Aux equipment is in the right location, as...
  3. C

    Intelliflo VSF pump won't run when connected to automation via iAqualink

    Hi. Thanks for this suggestion. I did check it and the Intelliflo VS pump is shown.
  4. C

    Intelliflo VSF pump won't run when connected to automation via iAqualink

    Thank you. I read this, and did confirm that the pump is set to speed (not flow) via the pump control pad. Also, the version of iAqualink I'm seeing did not show options for VF or VS when setting up the pump. Rather just the Intelliflo VS as an option to select, which I did.
  5. C

    Intelliflo VSF pump won't run when connected to automation via iAqualink

    Yes, continuous power to the pump independent of the PCB.
  6. C

    Intelliflo VSF pump won't run when connected to automation via iAqualink

    Thank you for the quick replies. Attached VSP Setup and Pump Speed pages. Thanks.
  7. C

    Intelliflo VSF pump won't run when connected to automation via iAqualink

    Installed Jandy iAqualink 3.0 (IQ30-RS) with new complete bezel & PCB Rev. Y. All the communication aspects work fine. Set up the pump in iAqualink as Pentair VS pump. Default pump speeds are set. While in auto mode, selecting on the app to start the filter pump initiates all the usual actions...
  8. C

    Bonding via brass conduit and existing niches for pool & spa light replacement

    Remodeling pool. Replacing original Amerlites with Jandy WaterColor LEDs. Existing niches are Pentair Stainless Steel, with brass conduit running from niches to metal J Boxes. Should I consider this setup good (sufficiently bonded) if I simply replace the lights and wire them in as the...