  1. B

    Pentair IntelliCenter

    Hello All, I have read through the thread and am completely confused. What is the big advantage with the new release? Thanks
  2. B

    Sub panel wiring

    Thanks for all the information. I will update how it goes.
  3. B

    Sub panel wiring

    Thanks for update on IntelliCenter release. Trying to figure out what is different. Load Calcs. Pump 1 3200 watts Pump 2 3200 watts Heat pump 7000 watts SWG 1500 watts Air blower 1400 watts Outlet 1500 watts Total 17,950 watts Total Amps 75 I understand...
  4. B

    Sub panel wiring

    A little more information. Replacing old (1979) 15x30 pool with new pool/spa. Main panel is 200 amp. Load calc with new equipment is 173 amp. Relocating equipment area. Hope equipment shows up in signat. Don't think I need the full 125 amp, put that is what the pentair I9 is rated for. Thought I...
  5. B

    Sub panel wiring

    I am looking to install the Pentair I9 Intellitouch (125 amp)sub panel. I will run about 60ft from main panel through attic/floor joist, then the last 20ft outside to a stand alone panel board. I have read many threads but still not clear on requirements. If I want the full 125 Amp available...