    Pump trips circuit breaker after hours of running

    Sorry for such a late late reply, things have been hectic at home and work. No Darn there was snow, 9 inches! We set some records. Onto the pool side; I replaced the circuit breaker a couple weeks ago and haven’t had any issues since. Thank you again for taking so much time to help me work...
  2. D

    Pump trips circuit breaker after hours of running

    Once this snow clears up I’ll check out everything you all are suggesting and post pictures.
  3. D

    Pump trips circuit breaker after hours of running

    I’ll have to swap the breaker in a few days after this cold snap. I think my wife would kill me if I turned off power to the house right now lol. I’ll make sure to come back with the results though. How would I determine a short to ground between the breaker and pump vs a short to ground issue...
  4. D

    Pump trips circuit breaker after hours of running

    Notes from pump start to discovered CB trip “Others” being the other circuit breakers on the panel. OAT dropped significantly throughout the day which reflects on temp readings. Dry day, no rain. Amperage measured with Klein CL220 Temps measured with Klein Infrared Thermometer. All measurements...
  5. D

    Pump trips circuit breaker after hours of running

    Thank you for the replies and help. I have a lot of reading to do to fully understand how this all works. For now I’ll continue to take an hourly amperage and CB temp reading and report back.
  6. D

    Pump trips circuit breaker after hours of running

    Within 30 minutes of starting up the pump. All baskets are cleaned of debris, filter is backwashed. I’m planning on starting it up today and taking an amperage read every hour to see when the load increase starts to happen, and if it consistently starts around the same timeframe.
  7. D

    Pump trips circuit breaker after hours of running

    I can take pictures later today, but 10 amp pump pulling 10 amps measured via clamp. Both electricians agreed that the CB is operating properly and recommended against changing saying, “I’ll happily take your money, but the breaker is working properly and changing it won’t do anything.” 15...
  8. D

    Pump trips circuit breaker after hours of running

    Hey everyone, I’m running out of ideas here. I’ve had two electricians come out and verify everything is working fine on the electrical side. It pulls the correct amperage, it never trips the GFCI outlet, it trips after/while raining and if it’s dry. I have a Doheny pump that’s maybe a month...