  1. A

    Pentair Woes

    The Pentair guys were here today. They replaced the wireless outdoor antenna and it all worked right away. Of course using the wireless is new in the system as it has always been hard-wired. I believe the board in the antenna took the "hit" vs the UOC and/or the screenlogic brick which always...
  2. A

    Pentair Woes

    Thanks. No spa side controls. The pump appropriately shows display not active and is getting the programs it's supposed to run. I've replaced all the wires again to all the devices and I'm going to replace the low voltage power supply in the power center and the power center for the chlorinator...
  3. A

    Pentair Woes

    I put a datalogger on the power lines on the 4 wire bus last night for 10 hours of logging. I know I'm probably all alone here with this problem.. I've been all alone and frustrated for years. If anyone has any additional thoughts, please share. I should add that the load center and it's...
  4. A

    Hooking up low voltage lighting to Omnilogic

    Those relays are likely 24vac coils? You could get a plastic or metal enclosure box and mount it next to the panel, then remove those relays and run the coil wires out of the main box via a low voltage runway/knockout/drill one and into the companion box. Then it should be compliant with only...
  5. A

    Pentair Woes

    Yes. I simply lose the ability to "talk" to the UOC. I'm quite sure something is killing the data or power on the 4 wire bus, but not sure what. I've been monitoring the 240V at the panel, and it is always 239-244 regardless of how many things turn on the same time, even hitting both A/C units...
  6. A

    Pentair Woes

    My next step is to put a voltage data logger on the power bus on the UOC and see if anything shows up. Won't tell me what is wrong, but maybe give a clue. Power supply? You mean the low voltage transformer in the load center?
  7. A

    Pentair Woes

    I have a i9+3S with IC40 and one of the original power packs (1 resistor) and Intelliflow VF. I have NEVER been able to keep communication for more than 45 days from the screenlogic to the panel. The shortest was 14 days, the most recent was 3 weeks (It's been 85 F +) last 3 weeks. This has...